23 Studio Air-Conditioning
Air Quality
Potential pollutants:
1. reduced oxygen and increased carbon dioxide from people;
2. water vapour, cigarette smoke;
3. formaldehyde from studio furnishings.
Ventilation Requirements
To maintain carbon dioxide at the maximum recommended level of 0.5 per cent by volume the minimum ventilation requirement is 0.8 l/s for seated persons.
Dilution of body odours to acceptable levels requires a fresh air ventilation rate of 8 l/s for sedentary non-smoking occupants. When heavy smokers are present the rate should be at least 32 l/s.
Thermal Comfort
Temperature
A person seated and at rest produces approximately 115 W of heat (75 per cent by radiation and convection, 25 per cent by evaporation).
The comfort of ...